Bugtraq mailing list archives

DoS vulnerability in Siemens S7-1200 PLCs


From: Arne Vidström <arne.vidstrom () foi se>
Date: Thu, 20 Dec 2012 17:07:13 +0100

Hi all,

I have found a DoS vulnerability in the Siemens S7-1200 PLCs. It is present in firmware versions 2 and 3. After an 
exchange of specially crafted packets to TCP port 102 the PLC shuts down. The red, green and yellow status LEDs start 
flashing. All outputs are shut off. The device stops listening at port 102 and becomes completely non-responsive. 
Sometimes a few status messages are sent before it shuts down. They state that a serious firmware error has occurred 
and that the PLC is defective. Power cycling the PLC restores operation though.

More information can be found in the Siemens advisory:

http://www.siemens.com/corporate-technology/pool/de/forschungsfelder/siemens_security_advisory_ssa-724606.pdf

Best regards /Arne

-

Arne Vidström
Swedish Defence Research Agency (FOI)
http://www.foi.se/en/Our-Knowledge/Information-Security-and-Communication/Information-Security


Current thread: