nanog mailing list archives

Re: MAE-East still no generator


From: Stephen Stuart <stuart () pa dec com>
Date: Sun, 08 Sep 96 10:53:47 -0700

On Sun, 8 Sep 1996, Avi Freedman wrote:

it to 110vac?  If not, we're probably going to have to build our own
battery rack and/or stick a generator on the roof at one of our MFS
colo sites.

Interesting enough, many fire departments won't allow roof mounted
generators anymore because storing fuel along with it is considered
hazardous.  We had an awful time getting our 250 kw generator installed
and ended up with it on the ground level next to the parking garage
with an integral fuel storage tank; it was the easiest to get permitted.

We solved that as PAIX by having the main fuel tank in the basement,
in a steel-reinforced cinder-block vault, with a "day tank" up on the
roof; a redundant pair of pumps draw fuel from the basement up to the
roof. The fire department liked it because there wasn't too much fuel
on the roof, and the (whatever that other department was) liked it
because the generator was on the roof (and the noise at ground level
wouldn't be too great during weekly tests).

Stephen
- - - - - - - - - - - - - - - - -