Date: Sun, 12 Sep 1999 15:14:08 -0700
Brad S. Dreisbach <bradd () dn net> wrote:
Im getting weird syslog messages about the temp. Ive never seen this from my router at 8100 boone. Sep 12 17:00:17 mae.dn.net 662: *Sep 12 12:58:40.754 UTC: %ENVM-4-ENVWARN: chassis outlet 3 measured at 50C/122F
What do other sensors show? If all temperatures are consistently high, there's a real environmental problem. Otherwise it could be a broken sensor (i've seen that happening with cisco gear several times), or a stuck fan in the box. In any case you'd better go there and check what's going on. --vadim