At 11:56 AM 7/22/2004, you wrote:
Have anyone experienced hardware failure related to electrical spikes coming into your datacenters or equipment locations via the telco facilities? I am referring specifically to copper facilities for DS1's, etc. I know that the telco must maintain good grounding, but sometimes when you get hit with a few Gigavolts worth of electrical energy not much will help you. Whatever the case, has anyone had any experience good or otherwise with surge protection for their Telcom circuits? I am looking at this unit below as a possible solution.
Rule #1, don't trust the telco or the power company, or anyone else feeding wires into your building to do a good job keeping you safe from surges.
A client of mine has what used to be a CSU/DSU... now has surface mount components missing and the like. They hadn't installed a surge protector on the T-1. They had covered the power and the antenna coaxes at the site. Only the T-1 line was unprotected. Lightning will find that one path you've not protected.
The cost of installing a surge protector is unlikely to impact your bottom line. One successful lightning strike on the other hand will hurt quite a bit, and probably happen at 4AM just to be more annoying.
Current thread:
- Surge Protection Fisher, Shawn (Jul 22)
- Message not available
- Re: Surge Protection Daniel Senie (Jul 22)
- Re: Surge Protection Mike Lewinski (Jul 22)
- Re: Surge Protection Scott McGrath (Jul 22)
- Re: Surge Protection Marshall Eubanks (Jul 22)
- Re: Surge Protection Daniel Senie (Jul 22)
- Message not available
- <Possible follow-ups>
- Re: Surge Protection Mike Nice (Jul 22)
- Re: Surge Protection David Lesher (Jul 22)