On Monday 24 March 2008, Deepak Jain wrote:
While I enjoy hand waving as much as the next guy... reading over this thread, there are several definitions of sq ft (ft^2) here and folks are interchanging their uses whether aware of it or not.
[snip]
A 30KW cabinet while one sounds lovely, a huge amount of space is going to turned over to most or all of a dedicated PCU and 1/15th of the infrastructure of 500KVA UPS (@0.9PF) including batteries, transformers, etc.
[snip]
Even ignoring heat rejection, the battery + UPS gear for 500KVA (even with minimal battery times) is approximately the same size (physically) as the 12 cabinets or so it takes to reach that capacity. [same applies for flywheel/kinetic systems]
This is certainly a fascinating thread. One thing I haven't seen discussed, though, is the other big issue with high-density equipment, and that is weight. Those raised floors have a weight limit. In our case, our floors, built out in the early 90's, have a 1500 lb per square inch point load rating, and 7,000 pound per pedestal max weight. The static load rating of 300 pounds per square foot on top of the point load rating doesn't sound too great, but it's ok; we just have to be careful. Our floors are concrete-in-steel, on 24 inch pedestals, with stringers. In contrast, a 42U rack loaded with 75 pound 1U servers is going to weigh upwards of 3,150 pounds (if you figure 300 pounds for the rack and the PDU's in the rack, make that 3,450 pounds). When we get to heavier than 75 pound 1U servers things are going to get dicey. Also in contrast, a fully loaded EMC CX700 is about 2,000 pounds. It sounds more and more like simply charging for rack-occupied square footage is an unsustainable business model. The four actual billables are power, cooling (could be considered power), bandwidth, and weight. When we see systems as dense as a Cray 2, but with modern IC's, we'll be treated to flourinert waterfalls again. :-) -- Lamar Owen Chief Information Officer Pisgah Astronomical Research Institute 1 PARI Drive Rosman, NC 28772 (828)862-5554 www.pari.edu
Current thread:
- Re: rack power question, (continued)
- Re: rack power question chuck goolsbee (Mar 25)
- Re: rack power question Petri Helenius (Mar 25)
- Re: rack power question Paul Vixie (Mar 25)
- Re: rack power question William Herrin (Mar 25)
- Re: rack power question Paul Vixie (Mar 25)
- Re: rack power question Petri Helenius (Mar 25)
- Re: rack power question Dorn Hetzel (Mar 26)
- Re: rack power question Petri Helenius (Mar 26)
- RE: rack power question John Lee (Mar 25)
- Message not available
- Re: rack power question Paul Vixie (Mar 25)
- data center loading (was:Re: rack power question) Lamar Owen (Mar 26)
- Re: data center loading (was:Re: rack power question) Robert Boyle (Mar 26)
- Re: rack power question Joe Greco (Mar 22)
- Re: rack power question david raistrick (Mar 22)
- Re: rack power question Patrick Clochesy (Mar 22)
- Re: rack power question Tony Finch (Mar 26)
- Re: rack power question Martin Hannigan (Mar 28)