On Wed, Mar 19, 2014 at 9:07 AM, Lamar Owen <lowen () pari edu> wrote:
2011 NEC article 210.23(A) permits 15A receptacles on 20A branch circuits;
30A branch circuits must use 30A receptacles.  If the OP's 30A branch
circuit has an L6-20R on it then this would be a violation; see NEC Table
210.24 for a summary of the code.

Hi Lamar,

Nobody is talking about putting an L6-20R on a 30 amp circuit. OP was
talking about putting an L6-30P on a 20 amp appliance: a PDU that has
its own 20 amp breaker. Big difference.

Regards,
Bill Herrin



-- 
William D. Herrin ................ herrin () dirtside com  bill () herrin us
3005 Crane Dr. ...................... Web: <http://bill.herrin.us/>
Falls Church, VA 22042-3004