nanog mailing list archives

Re: L6-20P -> L6-30R


From: Seth Mattinen <sethm () rollernet us>
Date: Wed, 19 Mar 2014 14:51:54 -0700

On 3/19/14, 10:21, Jay Ashworth wrote:
It is exactly that: no one says you*can't*  wire a 20A branch circuit with
#10.

It is even*possible*, though unlikely, that if you did so, you wouldn't
have to derate it to 80%.  I would have to reread the Code to be sure.

Well, I'd say it's pretty likely. However highly unlikely to be code-worthy of slapping on a 30A breaker in place of a 20. 10-20 CCCs in a raceway or cable is a 50% derating, so if those conductors were for 20A branch circuits it would have to be 10AWG, not 12 since with 10AWG you're derating from 40A. But the max protective device on 10AWG is 30A unless permitted by 240.4.

Even 7-9 CCCs in a raceway or cable derates 10AWG to 28A (70%), so while still suitable for a 20A breaker it's not for 30A. Max would be 6 CCCs to stay at 80% derating (4-6 CCCs).

~Seth


Current thread: