15kW is 1.5kVA in a simple radiant electric heat application. (it’s a simple resistive load with no power factor 
weirdness). Whether you could do this with 4-8kVA depends on what else you’re trying to run.



Owen


15kW is 15kVA (not 1.5 kVA) at a power factor of 1.0, if the heat is all resistive.